50 Ton 80 Hp 200 Kw Air Cooled Water Chiller Machine With Competitive Price
-
Payment
-
Origin
China Mainland
-
Minimum Order
1
-
Packing
Pieces
- Contact Now Start Order
- Description
Product Detail
50 Ton 80Hp Air Cooled Water Chiller Machine With Competitive Price
Anyda as the china water chiller manufacturer, have gradually produced Industrial Chiller,Water Chiller,Air Cooler,Oil Chiller,Low Temperature Chillers,Hot Water Chiller, Heat Pumps and Central Air Conditioner which are widely applied to plastic & rubber machinery, daily-use chemical, textile, general machinery, laser machinery, LCD and PCB industry, electroplating, equipments of laboratory, food, pharmacy, etc .
50 Ton 80Hp 200kw Air Cooled Water Chiller Machine Parameters:
Item |
Specifications |
|
Cooling Capacity |
Model |
AYD-200AS |
kw/h |
205.6 |
|
Power Input |
kw |
70 |
Outlet Temp |
degree |
7 |
Power Supply |
400V-3N-50HZ |
|
Refrigerant |
R407C |
|
Dimension(L*W*H) |
mm |
3180*1900*2060 |
Compressor |
Type |
semi-hermetic screw |
Power(kw) |
60 |
|
Condenser |
Type |
Finned |
Fan Power(kw) |
7 |
|
Air Volume(m3/h) |
86400 |
|
Evaporator |
Type |
Shell and Tubes |
Pipe Size(") |
3 |
|
Flow(m3/h) |
35.36 |
|
Protector Device |
1.Phase protector |
|
FAQ:
1.How to calculate cooling capacity for chillers
Cooling Capacity(kw)= Flow Rate(m3/h)*Temp Change(T1-t2)/0.86
Heat Load= C(specific heat)* M(quality output per hour )*Temp Change(T1-T2)
2.Types of chiller system?
Air Cooled Chiller and Water Cooled Chiller.Water cooled chiller needs a separated cooling tower and has a higher efficiency,but less easier than air cooled.
3. How to select the model of the chiller ?
It is better to tell us some parameter, such as : Cooling Capacity, Outlet Temperature, Power Supply,Environment Temperature, Application Field, Anti-rust Or Anti-corrosion, and so on.Meanwhile,we could do customized chiller according to your end user consumption.
4.Cooling capacity unit conversion?
1 kcal/h = 1.163W,1 W = 0.8598 kcal/h;
1 Btu/h = 0.2931W,1 W = 3.412 Btu/h;
1 USRT = 3.517 kW,1 kW = 0.28434 USRT;
1 kcal/h = 3.968 Btu/h,1 Btu/h = 0.252 kcal/h;
1 USRT = 3024 kcal/h,10000 kcal/h = 3.3069 USRT;
5. What is production period ?
Generally speaking, it is 15-30 days,some standard model there are some stocks, but it all depend on the model ,quantity.
6.What is your company after-sales service ?
Our warranty period is one year. If there is any problem in this year, we will send you the new parts (not including freight )for replacement. Meanwhile, welcome to consulting the technical knowledge.
- Packaged 30 Ton 40 HP 110 Kw Air Cooling Water Chiller With Copeland Compressor 1 Pieces / (Min. Order)
- 1 Hp Mini Instant Refrigerated Water Chiller Circulator 1 Pieces / (Min. Order)
- 2 Hp 1 Ton Small Electric Industrial Water Chiller Unit For Sale 1 Pieces / (Min. Order)
- 50HP 35Ton Integrated Copeland Scroll Compressor Water Chiller China Air Cooled For Soap Factory 1 Pieces / (Min. Order)
- 3 Ton 5 Hp Small Modular Air Cooled Scroll Water Chiller Unit 1 Pieces / (Min. Order)
- Packaged Air Cooled HVAC Air Conditioning Screw Water Chiller 1 Pieces / (Min. Order)
- 5 Ton 20 Kw 8 HP Industrial Plastic Extrusion Molding Machine Air Cooled Water Chiller System 1 Pieces / (Min. Order)